Systems
When one building needs more than a cabinet: the Power Container for facilities and bases, the Mobile Welding Power Unit for jobsites, and containers in parallel for whole campuses.
Behind the meter · 480 V three-phase
Power Container
Built to order4.8 MWh of lithium iron phosphate storage and 420 kW of 480 V three-phase power in one 43 ft high-cube container, built for the facility, not the substation.

How it works
- Seven independent inverters (Sol-Ark 60K-3P-480V) share the load, mounted outside the battery room.
- Twenty-five independent strings of twelve Shield HV modules, each with its own controller and contactors. If one string misbehaves, it is isolated and the other 24 keep carrying the load.
- Three NEMA 3R load centers, for loads, grid and generator. Each container ties into the facility through its own transfer switch.
- Grid-tied, off-grid or with a generator. 630 kVA of surge for 10 s for motor starting.
On site
- Arrives ready. Racks, cooling, fire protection and electrical gear are installed; modules ship separately and slide into place on site.
- No new foundation. Cross-driven spike anchors install on existing pavement for seismic restraint.
- N+1 cooling and filtered air. Two wall-mount A/C units and MERV 8 + 13 filtration under positive pressure.
- Status at the door. A 21.5 in, 1,000-nit display shows charge, power flow, temperatures and alarms.
Eight layers of protection
Engineered so that no single failure becomes an event. The shutdown is hardwired and fail-safe, so protection never waits on software or a network.
- MonitoringEvery cell's voltage and temperature, around the clock, with active balancing.
- Thermal imagingSix thermal cameras watch every tower face; infrared windows on the load centers.
- Off-gas detectionSensors catch cell vapor before smoke, backed by smoke and heat detectors.
- Rapid shutdownStrings open, inverters stop and mains trip in about 2 seconds.
- Fire separationTwo layers of 5/8 in Type X line the room, and Type X separates every tier.
- SuppressionSix total-flooding aerosol units protect the battery room. No water, no piping.
- Explosion controlPowered exhaust clears gas; four roof vent panels release pressure upward.
- Seismic anchoringCross-driven spike anchors on existing pavement. No new foundation.
Battery modules
- UL 1973 · UL 9540Certified
- UL 9540ATest method, testing completed
- UL 9540BPending
Each Power Container
NRTL field evaluation through IntertekDesign basis: NFPA 855, 68, 69, 70 and 72.
Need more? Add containers
Each container is a complete power plant with its own inverters, load centers and transfer switch into the facility's main gear. Every container runs independently, so one can be serviced while the rest keep running.
| Containers | Power | Energy | Current at 480 V |
|---|---|---|---|
| 1 | 420 kW | 4.8 MWh | 506 A |
| 2 | 840 kW | 9.6 MWh | 1,012 A |
| 4 | 1.68 MW | 19.2 MWh | 2,024 A |
| 6 | 2.52 MW | 28.8 MWh | 3,036 A |
Electrical and battery
- Energy
- 4.8 MWh nominal, LFP
- Power
- 420 kW continuous
- AC output
- 277/480 V, three-phase, 60 Hz
- Surge
- 630 kVA for 10 s
- Cells
- 4,800 × Hithium 314 Ah LFP prismatic
- Modules
- 300 Shield HV modules, 16.1 kWh each
- Towers
- 50 six-tier towers, 25 per side
- Strings
- 25 × 192 cells, 614 V nominal
Container and site
- Container
- 43 ft high cube (43 × 8 × 9.5 ft)
- Weight
- About 89,000 lb with modules installed
- Emergency stops
- 2: door end and equipment wall
- Detection
- 3 off-gas, 4 smoke, 4 heat
- Clearances
- 10 ft to combustibles; 3 ft working space
- Delivery
- Modules ship separately
- Options
- Solar canopy, generator with automatic start, 208 V transformer, EMP shielding for exterior gear, maintenance package
- Included
- Sentinel Pro, operator training, O&M manual and turnover package, 12-year warranty
Jobsite power · 480 V three-phase
Mobile Welding Power Unit
Built to orderA trailer-mounted high-voltage battery bank with one Sol-Ark 60K for 480 V three-phase welding and jobsite power, with no generator running on site.
Storage is sized to the job. Tell us the welders and tools you run and the hours you need.
Welding at 480 V
Three-phase power for welders on the trailer, where the work is.
Jobsite power
Tools, lighting and site trailers on the same 480 V service.
Same technology
The Sol-Ark 60K and the high-voltage LFP technology used across the AEGIS commercial line.
Monitored